Heat Pump Auxiliary Heat Strip Lockout During Polar Vortex Freeze in Pflugerville Pfarms

G
Gordon_W_PflugervillePfarms Homeowner
Posted in Pflugerville Homeowner Forum • Travis County

Question: During freezing 22-degree weather in Pflugerville Pfarms, our heat pump outdoor unit turned into a solid block of ice and the indoor vents began blowing cold 62-degree air. The thermostat read AUX HEAT but house temperature was falling. How does a heat pump defrost during Texas winter freezes?

βœ“ VERIFIED PRACTIONER DIAGNOSIS
T
Travis_H_EPA_Universal Texas TDLR Senior Diagnostics Tech
Texas Department of Licensing & Regulation Certified

The outdoor defrost control board temperature sensor failed open, preventing the reversing valve from switching into cooling mode to thaw the outdoor coil, while an open sequencer fuse disabled emergency heat strips.

Diagnostic Procedure & Field Restoration:

  • Outdoor ambient temperature dropped to 22 degrees Fahrenheit with 90% humidity, creating heavy frost accumulation.
  • Defrost thermostat sensor failed to close at 30 degrees, leaving the outdoor coil completely choked with ice.
  • Stage-2 electric heat sequencer auxiliary relay had blown an internal 5kW fusible link, leaving only 5kW of heating for a 2,400 sq ft home.
  • Replaced the defrost board and sensor, verified 4-way reversing valve shift into cooling mode to melt ice within 8 minutes, and restored full 10kW auxiliary heat strip staging.