TXV Thermal Expansion Valve Restriction vs Low Refrigerant Charge in Blackhawk Pflugerville

E
Evelyn_K_Blackhawk Homeowner
Posted in Pflugerville Homeowner Forum • Travis County

Question: Our 4-ton split AC system in Blackhawk runs continuously from 3 PM until 10 PM but will not cool below 78 degrees. Another company came out and suggested adding 4 pounds of R-410A refrigerant. How do technicians verify if the system has a real leak or if the thermal expansion valve is restricted?

βœ“ VERIFIED PRACTIONER DIAGNOSIS
T
Travis_H_EPA_Universal Texas TDLR Senior Diagnostics Tech
Texas Department of Licensing & Regulation Certified

Technicians simultaneous measured superheat (26 degrees F) and subcooling (16 degrees F). High subcooling proved adequate refrigerant was present in the condenser, but a restricted TXV power element was choking flow to the evaporator.

Diagnostic Procedure & Field Restoration:

  • High superheat (26 degrees F) with high subcooling (16 degrees F) confirms liquid refrigerant is stacking in the condenser.
  • If the system had a true refrigerant leak, subcooling would have collapsed below 5 degrees F.
  • Removed restricted factory TXV under dry nitrogen purge, installed genuine OEM bolt-on TXV, pulled vacuum down to 320 microns, and weighed in precise factory trim charge.
  • Superheat stabilized at 11.4 degrees F and subcooling at 10.2 degrees F with 18.5-degree Delta-T drop across the coil.